TAYBO 374 kW Air & Liquid Cooled Load Bank Test System

Typical Integration Scope

VR200 / NVIDIA NVL72 / NVL144

VR200 / NVIDIA NVL72 / NVL144

Load-bank configurations for rack-scale cooling tests across VR200, NVL72 and NVL144 deployments. Validate combined air and liquid heat loads, coolant-loop flow, pressure and temperature response through staged or full-load operation.

Key Engineering Inputs

01

Rated capacity and load split

374 kW total: 342 kW liquid load (4 × 85.5 kW modules) plus 32 kW air load. Adjustable ranges: 0.5–342 kW liquid and 0.5–32 kW air.

02

Power, controls and communications

Three-phase AC 400 V, 50/60 Hz. Local HMI and remote/group control; Modbus TCP and RS485/TCP. Monitors electrical and coolant operating data with trends and export.

03

Coolant flow and hydraulic interface

Rated flow 360 L/min; design flow 1.5 L/min per kW ±10% with PG25. DN50 quick-clamp inlet/outlet; maximum working pressure 1 MPa. Typical supply/return temperatures 30°C/40°C.

Product Value

Mixed-load thermal validation

Combines 342 kW of liquid-cooled load and 32 kW of air-cooled load for staged or full-load heat-rejection and cooling-response tests.

Configurable rack-scale coverage

Four 85.5 kW liquid-load modules support a range of adjustable load steps. Test configurations can be set up for VR200, NVIDIA NVL72 and NVL144 deployments.